IEC 2003, 3, rue de Varembé, PO Box 131, CH-1211 Geneva 20, Switzerland- 36 p.
This part of IEC 61850 specifies the specific communication service mappings for the communication between bay and process level and it specifies a mapping on a serial unidirectional multidrop point to point link in accordance with IEC 60044-8. This part of IEC 61850 specifies a mapping of the abstract service for the transmission of sampled values (as defined in IEC 61850-7-2) on a serial unidirectional multidrop point to point link in accordance with IEC 60044-8. It applies to the communication between merging units of electronic current (ECT) or voltage-transformers (EVT) and bay devices such as protection relays. If higher requirements on sampling rate, further sampled measured value data sets in addition to the universal data set, inter-bay communication and synchronisation apply, these will be covered by IEC 61850-9-23.